❄️ Chiller Cooling Output
1,000 kW
kW

Cooling output in kW. 1 ton = 3.517 kW. Check chiller nameplate or submeter.

tons

Enter tons and kW fills automatically. Synced inputs.

⚡ Power Consumption
192 kW
kW

Electrical power consumed by the compressor + auxiliaries. Check power meter.

🌡️ Operating Conditions
°F

Standard: 44°F leaving evaporator. Lower = less efficient.

°F

Standard: 85°F entering condenser. From cooling tower cold water.

85%

% of rated capacity currently running. Chillers are most efficient at 70–90% load.

$/kWh

US commercial avg: $0.10–$0.16/kWh. Check your utility bill.

COP: —
Coefficient of Performance — updates live as you type
kW/ton
EER
Rating
$/hr cost

Calculating chiller COP…


Chiller COP — What It Is and Why It Matters for Your Energy Bill

COP is the single most important number when comparing chillers. Here’s what it means in plain English — and how to use it to save money.

What Is COP?

COP stands for Coefficient of Performance. It tells you how much cooling you get for every unit of electricity you put in. A COP of 5 means for every 1 kW of electricity, your chiller produces 5 kW of cooling. Higher COP = more efficient = lower energy bills. A typical modern centrifugal chiller runs COP 5.0–7.0. An old, poorly maintained chiller might run COP 3.0–4.0. That difference adds up to thousands of dollars a year.

📊

COP vs kW/ton — What’s the Difference?

Both measure the same thing — chiller efficiency — just in different units. kW/ton is the US standard used in ASHRAE 90.1 and most chiller specifications. COP is used internationally and in engineering formulas. Lower kW/ton is better. Higher COP is better. They’re inversely related: COP = 3.517 ÷ kW/ton. A chiller rated at 0.60 kW/ton has a COP of 5.86. ASHRAE 90.1 minimum for a large centrifugal chiller is 0.660 kW/ton (COP 5.33).

💰

How Much Does COP Actually Cost You?

The difference between a 4.0 COP and a 6.0 COP chiller is massive over time. A 300-ton chiller running 2,000 hours/year at $0.11/kWh: COP 4.0 costs about $58,000/year in electricity. COP 6.0 costs about $39,000/year. That’s $19,000 saved annually. Over a 20-year chiller life, that’s $380,000 difference — just from choosing a more efficient unit. Upgrading an old low-COP chiller is often the single highest-ROI energy project in a commercial building.

🌡️

What Affects COP?

Several factors change your chiller’s COP in real operation. Condenser water temperature matters most — every 1°F rise in entering condenser water temperature costs about 1–2% in efficiency. Chilled water setpoint also matters — every 1°F rise in chilled water supply temperature saves 1–2% in energy. Load percentage affects COP too: centrifugal chillers are most efficient at 70–90% load, not at 100% or below 50%. Fouled heat transfer surfaces (scaling, biofilm) can cut COP by 15–20%.

📋

ASHRAE 90.1 Minimum Standards

ASHRAE 90.1 is the US energy efficiency standard for commercial buildings. It sets minimum chiller efficiency requirements. The 2022 version requires large centrifugal chillers to achieve at least 0.660 kW/ton (COP 5.33) at full load. The IPLV (Integrated Part Load Value) must meet separate part-load standards. Energy Star certified chillers significantly exceed these minimums. Most new high-efficiency chillers achieve 0.50–0.56 kW/ton (COP 6.3–7.0) under standard conditions.

🔄

IPLV — The Seasonal Efficiency You Should Care About

Full-load COP tells you efficiency at 100% capacity. But most chillers never run at full load — they spend most of their time at 25–75% load. IPLV (Integrated Part Load Value) measures efficiency across a range of load conditions. IPLV is almost always better than full-load kW/ton for centrifugal chillers because of variable speed drives that dramatically improve part-load efficiency. When comparing chillers, compare IPLV — not just full-load kW/ton.

📐 Chiller COP Calculation Formulas

COP = Q_cooling (kW) ÷ W_input (kW) EER = COP × 3.412 [BTU/hr per Watt] kW/ton = 3.517 ÷ COP [where 1 ton = 3.517 kW = 12,000 BTU/hr] COP = 3.517 ÷ (kW/ton) Annual Energy (kWh) = Power (kW) × Hours × Load Factor Annual Cost ($) = Annual Energy (kWh) × Electricity Rate ($/kWh) IPLV (kW/ton) = 0.01A + 0.42B + 0.45C + 0.12D [AHRI 551/591]

In the IPLV formula: A = kW/ton at 100% load, B = at 75%, C = at 50%, D = at 25%. Carnot COP_max = T_evap(K) ÷ (T_cond(K) − T_evap(K)). Real chillers achieve 50–70% of Carnot limit. For air-cooled chillers, EER is the standard metric. For water-cooled chillers, kW/ton and COP are standard. 1 kW/ton = 0.284 kW/kW = COP of 3.517. The factor 3.412 converts: 1 kWh = 3,412 BTU, so EER (BTU/Wh) = COP × 3.412.


Chiller Efficiency Benchmarks — ASHRAE 90.1-2022

Chiller TypeSizeASHRAE Min (kW/ton)Min COPGoodBest Available
Centrifugal (water-cooled)>300 tons0.600 kW/ton5.860.52–0.560.48–0.50
Centrifugal (water-cooled)150–300 tons0.660 kW/ton5.330.56–0.620.50–0.54
Centrifugal (water-cooled)<150 tons0.780 kW/ton4.510.64–0.720.56–0.62
Screw / Scroll (water-cooled)>150 tons0.720 kW/ton4.880.60–0.680.54–0.58
Reciprocating (water-cooled)All sizes0.800–1.200 kW/ton2.93–4.400.72–0.820.64–0.72
Centrifugal (air-cooled)>150 tons1.050 kW/ton3.350.90–1.000.82–0.90
Screw/Scroll (air-cooled)All sizes1.200 kW/ton2.931.00–1.100.90–1.00

Frequently Asked Questions

A good COP for a modern water-cooled centrifugal chiller is 5.5 to 7.0 at full load under ARI standard conditions (44°F chilled water supply, 85°F entering condenser water). Water-cooled chillers are significantly more efficient than air-cooled units. A good air-cooled chiller typically achieves COP 3.0–3.5. The ASHRAE 90.1 minimum for a large water-cooled centrifugal chiller (over 300 tons) is a COP of about 5.86 (0.600 kW/ton). Energy Star certified water-cooled chillers achieve COP 6.0 or better. If your chiller is below COP 4.5 under standard conditions, it’s likely old, fouled, or a less efficient type and a replacement study is warranted.
The conversion is simple: kW/ton = 3.517 ÷ COP. The number 3.517 is the kW equivalent of one ton of cooling (12,000 BTU/hr ÷ 3,412 BTU/kWh = 3.517 kW/ton). So if your chiller has a COP of 5.0, its kW/ton is 3.517 ÷ 5.0 = 0.703 kW/ton. Going the other direction: COP = 3.517 ÷ kW/ton. A chiller rated at 0.660 kW/ton has a COP of 3.517 ÷ 0.660 = 5.33. Our conversion calculator on the Conversions tab handles all these instantly.
COP and EER measure exactly the same thing — chiller efficiency — but in different unit systems. COP is dimensionless: it’s the ratio of cooling output (kW) to power input (kW). EER (Energy Efficiency Ratio) is in BTU/Wh: it’s the ratio of cooling output in BTU/hr to power input in Watts. The conversion is: EER = COP × 3.412 (where 3.412 BTU = 1 Wh). So a COP of 5.0 equals an EER of 17.06. EER is typically used for residential and light commercial equipment (window ACs, smaller systems). COP and kW/ton are more common for large commercial chillers. SEER (Seasonal EER) and IEER are seasonal versions that account for part-load efficiency.
Load percentage has a significant effect on chiller efficiency — and the relationship varies by chiller type. Modern centrifugal chillers with variable-speed drives are most efficient at 40–70% load, often achieving COP values 20–40% better than at full load. Fixed-speed centrifugal chillers are most efficient at 80–90% load. Screw and scroll chillers generally stay efficient across a wider load range. Below 25% load, most chillers become significantly less efficient and some cycle on/off (reducing efficiency further). This is why IPLV (Integrated Part Load Value) matters — it represents the weighted average efficiency across real-world load conditions, not just peak.
The savings depend on your current chiller’s COP, hours of operation, size, and electricity rate. As a rule of thumb, upgrading from COP 4.0 to COP 6.0 saves 33% of chiller electricity — because you’re using ⅓ less power for the same cooling. For a 300-ton chiller running 2,000 hours/year at $0.11/kWh, that’s roughly $19,000/year in savings. Over a 20-year chiller life (with a simple 5% escalation rate), the net present value of those savings can exceed $400,000 — easily justifying a premium for high-efficiency equipment. Use our Annual Energy Cost tab to calculate your specific savings scenario.
IPLV (Integrated Part Load Value) is a single efficiency number that represents a chiller’s performance across a range of operating conditions. It’s defined by AHRI Standard 551/591 and is calculated as a weighted average: IPLV = 0.01A + 0.42B + 0.45C + 0.12D, where A = efficiency at 100% load, B = efficiency at 75%, C = efficiency at 50%, and D = efficiency at 25%. The weights (1%, 42%, 45%, 12%) represent typical building operating hours at each load level. Most large commercial buildings spend very little time at full load — hence 50% and 75% load dominate the IPLV calculation. For chillers with VFDs, IPLV is dramatically better than full-load kW/ton. Always compare chillers using IPLV when selecting new equipment.
Bottom Billboard Ad — 970×250 (HVAC Engineers, High-intent exit placement)